PWR-AD10

SKU: PWR-AD10

IMS Power Supply Unit 100-240 V AC / 100-200 V DC

The PWR-AD10 module for Meinberg’s IMS platform is a highly efficient wide range power supply, accepting both 100-240 V AC and 100-200 V DC power. The power supply, designed for IMS system is hot-swappable and can be combined with other IMS PWR modules to form a redundant power solution for all components.

Key Features

AC/DC power supply module:

  • 100-240 V AC, 50-60Hz or 100-200 V DC input voltage.

Need help selecting the right solution?

Our technical specialists can help you choose the right product, answer technical questions and provide a quotation.

Contact an Expert

Technical Specifications

Operating Temperature 0 ... 50°C / 32 ... 122°F
RoHS Yes
Voltage Nominal Voltage:
100-240 V AC, 50-60Hz
100-200 V DC
Voltage Range:
AC: 90-265 V, 47-63 Hz
DC: 90-250 V

Output Current:
max. 10.0 A
min. 0.15 A

Fuse:
internal, T2.5A/250V

Protective Class:
Class 1
Power Consumption Pmax = 50 W
Electrical Connectors Power Connector: 5pin DFK
Further Information The extremely high efficiency of this module has been specifically designed by a world-class power supply manufacturer for Meinberg. The PWR-AD10 reduces thermal power loss to an absolute minimum.

A load sharing bus enables multiple power supplies to jointly generate power for an IMS system, ensuring continuous operation in case of a power supply failure or loss of a power source. It is possible to combine the PWR-AD10 with other power supply modules, for example a PWR-DC20, to use different input voltages from different power sources.
Hot Plug Feature It is possible to remove or install the power supply out of the terminal equipment during operation.
Relative Humidity Max. 85%
Status Info
  • LED: green, diameter 5mm, on if output OK
WEEE Status of the Product This product is handled as a B2B category product. In order to secure a WEEE compliant waste disposal it has to be returned to the manufacturer. Any transportation expenses for returning this product (at its end of life) have to be incurred by the end user, whereas Meinberg will bear the costs for the waste disposal itself.

Downloads

Datasheet Click to view Datasheet (PDF)